Sidewall

sidewall-sprinklers

Safex Standard Response Spray Sprinklers are intended for use in the Sprinkler Systems designed in accordance with the standard installation rules recognized by the applicable listing or approval agency. They are available in Pendent, Uprigh, Horizontal Sidewall Styles. Safex Quick Response Spray Sprinklers are designed with a 3mm glass-bulb to react quicker at the specified temperature. They are available in Pendent, Upright, Horizontal Sidewall Styles. During a fire conditions, the thermal-sensitive liquid in the Glass Bulb expands, causing the bulb to shatter, releasing the button and spring seal assembly. Water flowing through the Sprinkler orifice strikes the Sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire. Safex Standard and Quick Responders are designed for use in a wild range of applications including office buildings, libraries, hotels, restaurants, banks, band shells, theaters, factories, and storehouses.

Response: Standard/Quick Coverage: Water discharge is directed primarily outward and downward in a quarter spherical pattern, a portion of the spray is also directed towards the backwall.
Installation: Designed for installation along a wall or the side of a beam just beneath a smooth ceiling.(Ref.NFPA13)
Orifice Size: 1/2″/15mm Thread Size: ‘A” Pipe thread Temp. Rating: 135°F/57°C, 155°F/68°C 175°F/79°C, 200°F/93°C Maximum Service Pressure: 175 psig / 1.2MPa(12bar) Listings and ☆ Approvals: UL Finishes: Natural brass, chrome plate