Fiber System 8000 Controller

Home > Products > Fire Alarm System > Protectowire > Fiber System 8000 Controller
FiberSystem8000Controller

The Protectowire FiberSystem 8000 has been designed for use as a linear heat detection system using state-of-the-art fiber optic sensing technology. The system consists of Type PFS Fiber Optic Sensor Cable and the PTS Controllers with related software. The PTS Series Controllers can be configured for various alarm criteria and can be connected to an approved fire alarm control panel using relay inputs and outputs. The system is specifically designed for high risk commercial and industrial hazards that demand high relia- bility and customized system features.

Power Input:
DC Power Supply, 10 to 30 VDC
Power consumption: 17 W typical @ 20°C (68°F). Maximum power is < 40 W (under all operating conditions). UL listed systems require the use of an auxiliary 24 VDC power source capable of providing a minimum of 24 hours of standby emergency power with 10 minutes of alarm.

☆ Unique zoning capabilities. A single length of sensor can contain up to 256 zones.
☆ Multiple alarm initiating criteria by zone.
☆ Available with 1, 2 or 4 channels.
☆ Capable of continuous temperature monitoring in ranges up to 10km (32,800 ft.).